Please note this is NOT the old Excel brand, this is a new Excel brand and will not work with the old Excel range of products.
Excel 20A 1 Pole Type A RCBO B Curve 6kA – RCBO-120B-030
Part No Description
RCBO-120B-030 20A 1 Pole Type A RCBO B Curve 6kA
Residual Current Breaker with Over current.
Excel series Residual Current Breaker with Over current is mainly used in AC 50Hz with rated working voltage 230V and with rated current up to 40A. In case of personal electric shock or when the grid leakage current exceeds the specified value, the RCBO can work to quickly cut off the power supply within the very short time for protection of the safety of personnel and electrical equipment.
Suitable for industrial, commercial and domestic installations.
Product name | RCBO |
Standards | IEC61009-1 |
Certificate | CE, UKCA |
Electrical characteristics | |
Number of poles | 1P+N |
Rated frequency (Hz) | 50/60 |
Frame current (A)Inm | 40 |
Rated current (A)In | 6,10,16,20,25,32,40 |
Rated voltage (V) | AC230 |
Rated insulation voltage (V)Ui | 500 |
Rated impulse withstand voltage (kV)Uimp | 4 |
Rated short-circuit breaking capacity (kA)Ics | 6 |
Rated short-circuit breaking capacity (kA)Icn | 6 |
Instantaneous trip characteristics | B,C |
Trip form | Thermal, magnetic and Lekage trip |
Pollution level | 2 |
Rated residual action current (mA) | 30 |
Max. breaking time at the rated residual current | 0.1s |
Wave form of earth leakage sensed | AC / A |
Mechanical properties | |
Electrical life | 4000 |
Mechanical life | 10000 |
Protection grade | IP20 |
Indicator window | Contact status indication |
Normal operation conditions and installation characteristics | |
Storage temperature | -35℃ ~ +70℃ |
Installation site altitude | ≤ 2000m |
Terminals | Fixed with screw |
Maximum wiring capacity | In 16mm2 Out 6mm2 |
Maximum limit torque Nm | 3.5 |
Installation category | Class Ⅱ , Ⅲ |
Installation method | 35mm standard rail |
Incoming method | Upper and lower |